Series 150 Microprocessor RO Controller - NEMA 4X, 1HP Pump Output S 150

  • FREE SHIPPING to the Continental United States!

  • Financing Options Available at Checkout via Shop Pay & Paypal!

  • For Quantity Discounts Contact Us for a Quote!

  • For International Shipments Contact Us for a Quote!

  • Call: 1 (760) 598-0189

  • Email: hctivista@gmail.com

Please allow 1-2 weeks to ship

 

PLEASE REFERENCE DATA SHEETS AND TABLE BELOW

 

Series 150 Microprocessor RO Controller

 

Product Description

 

The Series 150 Microprocessor RO Controller provides comprehensive, reliable control for reverse osmosis (RO) systems. Engineered for OEM flexibility, this controller features advanced functionality suitable for various commercial and industrial applications.

The unit is equipped with a clear LCD display that delivers essential real-time operational feedback, including system status, water quality (TDS/conductivity), operating hours, and water temperature. Control is managed through five relay outputs, allowing direct operation of critical components such as the high-pressure pump (up to 1 HP single phase), inlet valve, and automatic flush valve.

Key control functions include monitoring for low and high-pressure switches, tracking storage tank levels (1-2 switches), and providing a pre-treatment lockout input. The Series 150 controller features temperature-compensated TDS/conductivity monitoring, ensuring accurate water quality readings for optimal system performance and water purity. Housed in a durable NEMA 4X enclosure, this controller offers robust protection for demanding environments.

 


 

Specifications Table

 

FEATURE SPECIFICATION / FUNCTION
Type Microprocessor Controller
Enclosure 8" x 6" x 4" NEMA 4X (Outdoor Use)
Power Input 102/240 VAC, 50/60 Hz, 25W
Display 2 x 20 LCD (Status, TDS, Temp, Hours)
Relay Outputs 5 (Pump, Inlet Valve, Flush Valve, Permeate Divert, Alarm)
Pump Motor Output 1 HP Single Phase (Max, Direct Drive)
Inputs 4 Dry Contact (L/H Pressure, Tank Level, Pre-Treat Lockout)
Monitoring Permeate TDS/Conductivity (Temperature Compensated)
Optional Inputs Feed TDS/Conductivity Monitoring
Key Features Automatic Flush, Pump Control, Tank Level Control

 

The series 150 Microprocessor controller has the features and options to allow OEM flexibility to meet many different specifications. the controller has five relay outputs, four dry contact inputs, and two TDS/conductivity inputs. A 2x20 LCD display provides the operating status of the RO unit along with the water quality, operating hours, and water temperature.

Features:
  • Relay outputs on the Series 150 controller operate the high pressure pump, inlet valve, flush valve, permeate divert valve, and remote alarm.
  • The relay for the high pressure pump can operate a 1HP single phase pump motor directly without an external motor controller.
  • Controllers for higher power pump motors are available upon request.
  • Dry contact input control the start and stop of the RO unit by monitoring the inlet pressure, tank level and pretreatment equipment.
  • permeate monitor and sensor are temperature compensated.
Monitoring and/or control of:
  • RO high pressure pump motor
  • Inlet solenoid valve
  • Automatic flush solenoid valve
  • Low feed pressure switch
  • High pump pressure switch
  • RO storage tank level switches (1-2)
  • Permeate TDS conductivity
  • Water temperature
  • Pre-treat lockout
  • Operating hours
Specifications: Inputs/outputs switch inputs: Optional:
  • Power: 102/240 VAC, +10 -15% 50/60Hz, 25W
  • Enclosure: 8" x 6" x 4" NEMA 4X
    (Enclosure may be larger to accept motor starters)
  • Pump relay (120/240V, single phase 1HP)
  • Flush valve relay
  • Inlet valve relay
  • Feed TDS/conductivity monitoring
  • I/O expander:
    • Tank low swtich input
    • Permeate divert or remote alarm relay
    • Aux relay